型号 |
8 |
10 |
12 |
15 |
20 |
25 |
8*2 |
10*2 |
12*2 |
15*2 |
20*2 |
25*2 |
|
| |
SM090 |
SM125 |
SM148 |
SM185 |
SM240 |
SM300 |
|
|
|
|
|
|
|
| |
名义制冷量 |
制冷量KW |
25.4 |
33.6 |
41.3 |
54.0 |
73.2 |
92.4 |
50.7 |
67.3 |
82.6 |
108.0 |
146.4 |
184.8 |
|
| |
输入功率KW |
4.3 |
5.7 |
7.0 |
9.0 |
12.2 |
15.4 |
8.6 |
11.4 |
14.0 |
18.0 |
24.4 |
30.8 |
|
| |
过渡 季节 |
制热量 KW |
25.2 |
34.4 |
39.5 |
52.7 |
71.9 |
90.6 |
50.4 |
68.8 |
79.0 |
105.4 |
143.8 |
181.2 |
|
| |
输入功率KW |
6.0 |
8.2 |
9.8 |
12.4 |
17.1 |
21.4 |
12.0 |
16.3 |
19.6 |
24.8 |
34.1 |
42.9 |
|
| |
地下水 名义 制热量 |
制热量KW |
30.6 |
41.3 |
50.0 |
64.5 |
88.9 |
111.8 |
61.2 |
82.6 |
100.0 |
129.0 |
177.8 |
223.6 |
|
| |
输入功率KW |
6.0 |
8.1 |
9.8 |
12.4 |
17.1 |
21.5 |
12.0 |
16.2 |
19.6 |
24.8 |
34.2 |
43.0 |
|
| |
地环路 名义 制热量 |
制热量KW |
23.8 |
32.4 |
38.5 |
49.6 |
68.0 |
85.7 |
47.6 |
64.8 |
77.1 |
99.1 |
136.1 |
171.4 |
|
| |
输入功率KW |
5.8 |
7.9 |
9.4 |
11.8 |
16.2 |
20.4 |
11.6 |
15.8 |
18.8 |
23.6 |
32.4 |
40.8 |
|
| |
工质 |
R22 |
|
| |
压缩机 |
全封闭涡旋式(百福马) |
|
| |
电源 |
3φ-380V-50Hz |
|
| |
安全保护 |
逆相保护、过流保护、高低温保护、高低压保护、水流保护 |
|
| |
制冷回路 |
1 |
2 |
|
| |
能量级别 % |
0,100 |
0,50,100 |
|
| |
制冷剂充注量Kg |
3.8 |
4 |
4.5 |
5 |
6 |
7 |
7.6 |
8 |
9 |
10 |
12 |
14 |
|
| |
冻水 |
进出水温度℃ |
12℃/7℃ |
|
| |
流量m3/h |
4.4 |
5.8 |
7.1 |
9.3 |
12.6 |
15.9 |
8.7 |
11.6 |
14.2 |
18.6 |
25.2 |
31.9 |
|
| |
管径DN |
40 |
40 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
65 |
65 |
80 |
|
| |
地下水 |
进出水温度℃ |
18℃/29℃ |
|
| |
流量m3/h |
2.5 |
3.3 |
4.0 |
5.3 |
7.1 |
9.0 |
4.9 |
6.6 |
8.1 |
10.5 |
14.2 |
18.0 |
|
| |
地环路 |
进出水温度℃ |
25℃/30℃ |
|
| |
流量m3/h |
5.1 |
6.9 |
8.3 |
10.6 |
14.5 |
18.3 |
10.2 |
13.9 |
16.5 |
21.2 |
29.0 |
36.6 |
|
| |
地热源管径 DN |
40 |
40 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
65 |
65 |
80 |
|
| |
生活热水流量m3/h |
4.3 |
5.9 |
6.8 |
9.1 |
12.4 |
15.6 |
8.7 |
11.9 |
13.6 |
18.2 |
24.8 |
31.2 |
|
| |
产50℃热水量 m3/h |
0.6 |
0.8 |
1.0 |
1.3 |
1.8 |
2.2 |
1.2 |
1.7 |
1.9 |
2.6 |
3.5 |
4.5 |
|
| |
生活热水管径DN |
40 |
40 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
65 |
65 |
80 |
|
| |
整机重量kg |
335 |
360 |
395 |
445 |
585 |
640 |
730 |
900 |
1050 |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
注: 1、制冷状态的参数以地下水进出温度为18/29℃时选取;地下环路进出水温度为25/30℃ |
|
|
|
| |
2、制冷状态时使用侧冻水温度为5~20℃; |
|
|
|
|
|
|
|
|
|
| |
3、制热状态的参数以地下进水温度为15℃,地下环路进水温度为0℃;出水温度由标准流量确定。 |
|
|
| |
4、制热状态时,使用侧进水温度40℃,出水温度由标准流量确定,热水最高温度为55℃; |
|
|
|
| |
5、规格性能参数会因产品改良而有所改变,恕不另行通知; |
|
|
|
|
|
|
| |
6、因产品改良,尺寸数据变化恕不另行通知。 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
“J&H”三联供机组是庄合近年来结合多种传统机型的优势,与德国BWP机构联合研发,攻克冷媒流量分配平衡(Refrigerant flow Balancing)等技术难题,耗时两年开发的高效、多功能高端产品。适合别墅、酒店、学校、会所、游泳馆。